Private Villa

ETFE single layer, Khobar Saudi Arabia

Area500 m²
FabricETFE
CityKhobar
Year2023
SectorResidential

Project overview

This private villa in Al Khobar has a courtyard roof of clear, un-printed single-layer ETFE covering more than 500 m². TMSI's scope was design, supply and installation, and the project is dated 2023.

The clear foil was chosen to bring as much daylight as possible into the enclosed courtyard. The membrane sits on curved tubular steel arches that were rolled and welded in the TMSI factory, and a stainless steel cable net runs with the curvature to control deflection under wind uplift. An integrated aluminium perimeter clamping system holds the foil and provides a continuous water seal.

Because it is a single-layer system, the roof has no mechanical plant and no power requirement — a passive, low-maintenance installation. The roof geometry was set by form-finding and analysed for wind, uplift and thermal load; panels were then patterned, thermally welded and inspected in the Dammam factory before being installed, tensioned, sealed and water-tested on site, with curvature checked so that no ponding can occur.

PROJECT 01

ETFE Single Layer — Clear · Al Khobar, Saudi Arabia

Project data

Project data
ProjectPrivate Villa
LocationAl Khobar, Saudi Arabia
SystemETFE single layer, clear
Approx. area500+ m2
Foil finishClear, un-printed
RestraintStainless steel cable net
StructureCurved tubular steel arches
ScopeDesign, supply and install

Scope of works

  • Structural design and form-finding of the courtyard roof
  • Fabrication of curved tubular steel arches and secondary members
  • ETFE panel patterning, welding and quality testing
  • Aluminium perimeter extrusion and cable restraint system
  • Site erection, membrane installation, tensioning and sealing

System description

  1. 01Single skin ETFE welded membrane, clear foil, maximising daylight into the enclosed courtyard.
  2. 02Fully integrated aluminium perimeter clamping system with continuous water seal.
  3. 03Stainless steel restraint cables running with the curvature to control deflection under wind uplift.
  4. 04Curved tubular steel arch structure, rolled and welded in the TMSI factory.
  5. 05No mechanical plant and no power requirement — a passive, maintenance-light installation.

Private Villa — Fabrication & Installation

Every panel is engineered, patterned and welded in our Dammam factory, then delivered to site as a finished, numbered assembly. The sequence below follows the actual production and installation route used on this project.

  1. 01 Form Finding & AnalysisRoof geometry is generated by form-finding, then analysed for wind, uplift and thermal load. Curvature, cable spacing and pre-stress are fixed here.
  2. 02 Steel FabricationTubular sections are rolled to the design radius, welded into arch segments and dimensionally checked against the setting-out drawing.
  3. 03 Patterning & CuttingThe curved surface is developed into flat cutting patterns with compensation for foil elongation, then plotted and cut to the panel schedule.
  4. 04 Thermal WeldingSeams are thermally welded under controlled temperature and pressure, with a keder edge welded to the perimeter. Every weld is inspected before release.
  5. 05 Steel ErectionArches are craned into position, aligned and bolted to the prepared bases, with temporary bracing retained until the frame is closed.
  6. 06 Extrusion InstallationSecondary members and the aluminium perimeter extrusion are fixed, levelled and surveyed to confirm the clamping line before any foil is opened.
  7. 07 Cable RestraintStainless steel restraint cables are installed and tensioned to the calculated pre-stress, forming the working surface for the membrane.
  8. 08 Membrane InstallationPanels are unrolled, the keder edge is fed into the extrusion and the foil is progressively tensioned. Clamping plates are torqued in sequence.
  9. 09 Sealing & Water TestPerimeter seals, flashings and rainwater details are completed and water-tested. Curvature is verified so that no ponding can occur.
  10. 10 Inspection & HandoverFinal visual and dimensional inspection, cleaning, as-built records and the operation and maintenance manual are issued at handover.

DESIGN & ENGINEERING

Private Villa – Design & Engineering

Brief Description — Structural Concept & Roof Geometry

Structural model of the villa courtyard roof: plan, elevation and isometric views of the two curved arch bays with their supports.
Structural concept and roof geometry

Loadings — Dead, Live & Wind Load (100 km/h, SBC 301)

Analysis model with the live load applied over the whole roof surface, annotated 0.24 kN/m².
Live load case — 0.24 kN/m²
Analysis model with the wind load case applied to the roof, load arrows shown over both bays.
Wind load case — 100 km/h per SBC 301

Support Reactions & Cable Design — Internal Forces

Member internal forces diagram for the cable net, maximum and minimum values of result combinations CO1 to CO26 shown along each cable.
Members internal forces N — result combinations, max and min values
Support forces and support moments — 3 rows
Support forces and support moments
Node No.LC/COSupport Forces [kN]Support Moments [kNm]
P X'P Y'P Z'M X'M Y'M Z'
CO470,4328,23-6,860,000,000,00
CO48-5,1330,94-7,400,000,000,00
CO490,4328,23-6,860,000,000,00

Cable Design — Member Sizing

Definitions, symbols and values — 28 rows
Definitions, symbols and values
DefinitionsSymbolUnitValueFormulation
Cable tensionNges[kN]47,39
Quantity of cablesn[-]1
Cable tension in the single cableNseil[kN]47,39
Design CriteriaLRFD
Load Safety Factorγf[-]1,00
Material Safety FactorγR[-]1,00(usually 1.0)
Cable Type1x19
Cable Diameterd[mm]12
Tensile StrengthRr[N/mm²]2160
Youngs Modulus for variable actionEQ[kN/cm²]15000
Filling load factorf[-]0,760
Equavalent Diameter Factorfed[-]0,872
Equavalent Diameter (Sap2000)de[mm]10,46=de*fed
Reduction dirillingk[-]0,880
Self Weight factorw[kg/cm²]0,830
Breaking Load FactorK[-]0,525= pi*f*k/4
Metallic Cross Sectional AreaAm[cm²]0,860
Nominal Metallic Areac FactorC[-]0,600
Stifness Single CableEA[MN]12,893
Stifness All cablesEAges[MN]12,893
Cable Weightg[kg/m]0,71=Am*w
Minimum Breaking Load CableFmin[kN]124,1= K*d2*Rr/1000
Socet TypeSwaged Socket
Loss factor (Due to cable fitting)ke[-]0,90
Characteristic value of the resistanceFuk[kN]121,0=Fmin*ke
Design Value of the cable tensionFEd[kN]47,39=Nseil*γf
Design value of the cable resistanceFrd[kN]80,67=Fuk/1.5*γR
Verification in the ultimate limit stateFed/Frd[-]0,59OK

Cables 12 mm stainless steel.

ETFE Foil Design — Material Properties & Warp Direction

This means ideally that the pretension in single layer ETFE foil structures should not exceed 3 MPa (for 250 micron 0.75 kN/m) and permanent high load like snow should be avoided. The breaking strength of ETFE foil is 50 MPa. However the elongation at the tensile strength level (tensile strain at break) is 500%. That’s why the breaking strength can not be used for design. In the design tensile stress at 10 % strain has been taken into account (23 MPa). The thickness of ETFE foil is 0.25 mm (250 micron). For 250 micron foil, the tensile stress at 10 % strain equals to 5.75 kN/m. The safety factor is taken into account as 1.5 for short term load (e.g. wind loading).

Membrane force plot in the warp direction across the ETFE panels, with the colour scale and the note that the maximum stress is 3.58 kN/m.
Warp direction — max n-x 3.58 kN/m, less than 5.75/1.4 = 4.1 kN/m (OK)
ETFE foil — material properties — 17 rows
ETFE foil — material properties
PROPERTYTEST METHODUNITMEAN VALUE
General
Specific GravityASTM D 792g/cm³1.75
Optical (200 µm film, clear)
Light TransmissionDIN EN 410%> 91
Colour Rendering IndexDIN EN 410-98.8
Shading CoefficientDIN EN 410-1.063
Solar Heat Gain CoefficientDIN EN 410-0.925
Mechanical
Tensile StrengthDIN EN ISO 527-1 (MD/TD)MPa50
Tensile strain at breakDIN EN ISO 527-1 (MD/TD)%500
Tensile stress at 10 % strainDIN EN ISO 527-1 (MD/TD)MPa23
Tensile Modulus (0,05-1%)DIN EN ISO 527-1 (MD/TD)MPa1000
Tear resistanceDIN 53363 (MD/TD)N/mm400
Thermal
Thermal Service Range°C-200 - 150
Melting PointASTM D 4591°C265
Shrinkage 150 °C/10 min%0 - 5

ETFE Foil Design — Weft Direction Forces

Membrane force plot in the weft direction across the ETFE panels, with the colour scale and the note that the maximum stress is 3.41 kN/m.
Weft direction — max n-y 3.41 kN/m, less than 5.75/1.4 = 4.1 kN/m (OK)

Fabrication — Cable Pose & Aluminum Profile Layout

Fabrication layout of the roof showing every cable pose and every base and inner aluminium profile numbered with its piece count.
Cable pose and aluminium profile layout — profiles divided into 2 or 3 pieces to suit air cargo, pose numbers marked on the profiles